This document outlines the specifications of the B900SE3-AU model in the PowerLink generator series, detailing design standards, operating conditions, factory inspections, painting process, general features, and equipment specifications.
B900SE3-AU
Standards & Conditions
- Design Standards: Complies with CE, ISO8528-5:2005, AS 3000-2018, AS 3010-2017.
- Environmental Operating Conditions:
- Installation: Suitable for outdoors or well-ventilated indoors.
- Temperature Range: -25℃ to 45℃ (coolant heater needed below 5℃).
- Humidity: Less than 90%.
- Altitude: Below 1000 meters.
General Features
- Components:
- Engine: Baudouin 8M33G4D3/5.
- Alternator: Leroy Somer LSA49.3L9.
- Control Module: PLC-500.
- Circuit Breaker: ABB 1600A 4P.
- Additional features: Speed governor (ECU), excitation system (AREP), AVR Model D350, key switch, emergency stop switch, ATS receptacle, remote run connector, maintenance-free batteries, etc.
Equipment Specification
- General Technical Data:
- Model: B900SE3-AU
- Tank Capacity: 1650L
- Dry Weight: 7250kg
- Noise Level @7m: 78dBA
- Dimensions: 4968x1869x2581mm
- Power: Standby Power 990kVA/800kW, Prime Power 900kVA/720kW
- Voltage: 380V, 400V, 415V
- Fuel Consumption: Details at various loads (25% to 110%).
- Diesel Engine Specifications:
- Manufacturer: Baudouin
- Model: 8M33G4D3/5
- Specifications include cylinders, bore, stroke, displacement, compression ratio, injection type, intake system, cooling system, battery voltage, fuel and oil type, capacities, back pressure, power ratings, fuel consumption.
- Alternator Specifications:
- Manufacturer: Leroy Somer
- Model: LSA49.3L9
- Specifications cover exciter type, cooling fan, windings, insulation class, winding pitch, terminals, drip proof rating, altitude limit, overspeed limit, air flow, voltage regulation, harmonic specifications, telephone interference.
Control System
- PLC-500 Control System:
- Microprocessor-based unit for genset protection and breaker control.
- Functions include monitoring operational parameters, indicating status and fault conditions, multiple protections, display features, manual/automatic/remote work modes, RS232 & RS485 communication, real-time clock, runtime display, load sharing capabilities.